The diesel dewatering pump used in
buildings include trailer mounted pump, diesel trash pump, trailer mounted pump and
horizontal sewage pumps. Because the general site in the building is small and
the displacement is not large, the submersible sewage pump and the submerged
drainage pump can be preferentially used in the drainage pump. The submerged
sewage pump is generally used in important places; the vertical sewage pump and
the horizontal sewage pump are required to be separated. The earthquake
foundation, self-priming water absorption, and occupying a certain site, it is
less used in the building.
Same as diesel engine irrigation pump.
The flow rate of the dieseldewatering pump should be selected according to the second flow
rate of the domestic drainage design; when the displacement is adjusted, it can
be selected according to the maximum hourly flow rate of the domestic drainage.
The flow rate of the drainage pump in the fire elevator collection pool is not
less than 10L/s.
The
lift of the drain pump is calculated according to the height of the lift and
the loss of the pipeline, and then a certain free head is attached. The free
head should be 0.02 ~ 0.03MPa. The flow rate of the suction pipe and the outlet
pipe of the drain pump should not be less than 0.7m/s, and should not be
greater than 2.0m/s.
In
the public building, a spare pump should be set up in each living drainage
basin as a unit, and it should be operated interactively. Drainage in the
basement, equipment room, garage flushing floor. If there are two or more
drainage pumps, the pump may not be used. When the collecting basin cannot be
equipped with an accident drain, the pump should have an uninterrupted power
supply; when the drain inlet can be closed, there is no need for uninterrupted
power supply, but an alarm device should be provided.
When
lifting sewage and wastewater with large impurities, the outlet pipes of
submersible sewage pumps in different collection pools should not be combined
and discharged; when upgrading general wastewater, the discharge pipes of
submersible sewage pumps of different collection basins can be considered and
combined according to actual conditions. .
When
two or more pumps share a single outlet, valves and check valves should be
installed on each pump outlet. When a single pump drain may cause backflow, a
check valve shall be provided. It is not allowed to combine the pressure drain
with the gravity drain in the building.
When
the submersible sewage pump is lifted to contain large debris, the submersible
sewage pump should be equipped with a crushing device; when lifting more sewage
containing more fibrous materials, a large-channel submersible sewage pump
should be used.
When
the submersible sewage pump motor power is greater than or equal to 7.5kW or
the outlet pipe diameter is greater than or equal to DN100, the pump can be
used to fix the auto-coupling device; when the submersible sewage pump motor
power is less than 7.5kW or the outlet pipe diameter is less than DN100, soft
can be set. Tube mobile installation. When the sewage collection basin is
drained by the submersible sewage pump, a water pump fixed auto-coupling device
shall be provided to facilitate the inspection of the water pump.
The
engine driven water pump should be able to start and stop automatically and
manually start and stop on site. Multiple pumps can be operated in parallel or
in sections.