According to the fire alarm signal or the failure of the electric fire pump to
start or the low pressure signal of the fire hose network, the engine driven
water pump will automatically starts, and manual operation is required after
the automatic start.
--Start
the pump in manual button
--
Main fire screen (located in the control room) manual button remote start
diesel pump
--
Manual button to stop diesel engine pump in fire pump room
--
Main fire screen (located in the control room) manual button remote control
stop diesel water pump
GU320A
intelligent liquid crystal display automatic controller, mainly has the
following control, fault protection and operating parameter detection
functions:
Control
method
The
controller has three control modes: automatic operation mode, manual operation
mode, and test operation mode. The controller has six buttons:
"AUTO": automatic mode, "MAN": manual mode,
"TEST": test mode, "START": start, "STOP/RESET":
stop, "L.TEST/MUTE": Test light and silence
Automatic
mode
Press
and hold the “AUTO” button (for more than 2 seconds), the LED on the button
lights up, and the controller runs in the automatic operation mode. When a fire
alarm occurs (passive normally open contact closure signal), the “START/Start”
button indicator lights up and a start signal is issued and the unit will start
automatically. If the unit fails to start within 10 seconds, it will stop after
10 seconds. If it cannot be started three times in a row, the LCD will display
“START FAILURE”. When the diesel engine water pump speed exceeds the starting
successful speed, the starter motor exits and the liquid crystal display is
“RUN/Run”.After the unit is automatically started, it can only be manually
stopped.
Manual
mode
Press
and hold the “MAN” button (for more than 2 seconds), the LED on the button
lights up, and the controller runs in manual operation mode. Press and hold the
"START" button (for more than 2 seconds), the start signal will be
sent and the unit will start. If the unit fails to start within 10 seconds, it
will stop after 10 seconds. If it cannot be started three times in a row, the
LCD will display “START FAILURE”. Press and hold the "STOP" button
(for more than 2 seconds), a stop signal will be sent and the unit will stop.
Early
warning and fault protection shutdown
Early
warning Note: The warning is a non-serious fault condition. Generally, some
detection parameters are close to the set value of the unit fault. The warning
is used to remind the operator to pay attention to the situation that does not
meet the requirements and solve it in time to ensure continuous operation of
the system. When the warning occurs, the status indicator lights up, the buzzer
sounds, but the fault is not locked, the unit does not stop, and the warning
light is automatically extinguished once the fault is removed. Warnings will
occur in the following cases: charging failure, low battery voltage, low oil
pressure, high engine cooling water temperature, overspeed, low speed
Downtime
failure
Alarm
and shutdown protection will occur when the unit has the following faults:
overspeed
Operation
parameter detection (liquid crystal status bar display) Oil pressure KPA Cooling
water temperature °C Oil machine running speed RPM Oil machine cumulative
running time H Battery voltage V Automatic control panel, mainly including the
following appliances:
Water
temperature meter Oil pressure gauge Manual start key GU320A intelligent liquid
crystal display automatic controller Automatic standby function. Battery
automatic backup charging (24.5V to 28.5V). Automatic cooling machine
preheating. The automatic standby state requires 220V and 2KW mains. The
terminal box next to the machine mainly includes the following appliances.Mains
charger auxiliary system
Fuel
and oil system
-
Oil filter (machine belt) Fuel filter (machine belt) DC starting system -Configure
DC 24V starter motor and 24V charging generator -24 volt, 120AH maintenance
free battery intake and exhaust system- dry air filter-Industrial silencer-
bellows Cooling system-Cooling fan, cooling water tank base frame Diesel
engine, water pump, cooling water tank, self-control screen, etc. are installed
on the same steel structure base frame. Random spare parts, random tools (as
specified by diesel manufacturers)
Operating
requirements for the use of diesel driven water pump before starting
When
preparing to start the diesel water pump(such as, diesel dewatering pump, diesel engine irrigation pump, trailer mounted pump, diesel trash pump)for the first
time, check the installation of all equipment and start as follows: Inject oil
from the fuel filler into the diesel engine and pump suspension, and check the
oil level with a dipstick to meet the required height. Add cooling water from
the expansion tank to the diesel engine. The water level should be 2/3
expansion tank. Put the diesel in the fuel tank, press the exhaust hand
pressure pump, and let the diesel enter the machine through the filter. Connect
the water pump inlet and outlet pipes and gate valves, close the gate valve of
the water outlet pipe, the outlet pressure gauge and the vacuum pressure gauge.
Fill water or vacuum water into the pump and inlet pipe and drain the internal
air. Open the external circulation cooling water valve.
·
When the inlet valve is fully open and the outlet valve is closed, the diesel
water pump is started. When the diesel engine reaches the normal speed, the valve
on the outlet pipe is gradually opened and adjusted to the required working
condition;